Environmental specifications
Specification | Value |
---|---|
Temperature range1 | — |
Operating | 10°C to 35°C (50°F to 95°F) |
Nonoperating | -30°C to 60°C (-22°F to 140°F) |
Relative humidity (noncondensing) | — |
Operating | 10% to 90%
28°C (82.4°F) maximum web bulb temperature |
Nonoperating | 5% to 95%
38.7°C (101.7°F), maximum wet bulb temperature |
1
All temperature ratings shown are for sea level. An altitude derating of 1.0° per 304.8 m (1.8°F per 1000 ft) to 3048 m (10,000 ft) is applicable. No direct sunlight allowed.
For certain approved hardware configurations, the supported system inlet temperature range is extended:
- 5°C to 10°C (41°F to 50°F) and 35°C to 40°C (95°F to 104°F) at sea level with an altitude derating of 1.0°C per every 175 m (1.8°F per every 574 ft) above 900 m (2953 ft) to a maximum of 3050 m (10,000 ft).
- 40°C to 45°C (104°F to 113°F) at sea level with an altitude derating of 1.0°C per every 125 m (1.8°F per every 410 ft) above 900 m (2953 ft) to a maximum of 3048 m (10,000 ft).