-48VDC Hot Plug Power Supply

Specification Value
Input requirements
Rated input voltage

-40 VDC to -72 VDC

-48 VDC nominal input

Rated input current

38 A at -48 VDC

25 A at -72 VDC

Rated input power (W)

1670 W at -48 VDC to -60 VDC

Rated input power (BTUs per hour)

6337 at -48 VDC

6094 at -72 VDC

Power supply output
Rated steady-state power 1500 W at -48 VDC to -60 VDC
Maximum peak power 1500 W at -48 VDC to -60 VDC
WARNING: To reduce the risk of electric shock, be sure that the cable grounding kit is properly installed and connected to a suitable protective earth terminal before connecting the power source to the server blade.

WARNING: To reduce the risk of electric shock or energy hazards:
  • This equipment must be installed by trained service personnel.
  • Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit has no direct connection to a primary circuit and derives its power from a transformer, converter, or equivalent isolation device.
CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to the earthing conductor at the equipment.

If this connection is made, all the following must be met:

  • This equipment must be connected directly to the DC supply system earthing electrode conductor or to a bonding jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode conductor is connected.
  • This equipment must be located in the same immediate area (such as adjacent cabinets) as any other equipment that has a connection between the earthed conductor of the same DC supply circuit and the earthing conductor, and also the point of earthing of the DC system. The DC system must be earthed elsewhere.
  • The DC supply source is to be located within the same premises as the equipment.
  • Switching or disconnecting devices must not be in the earthed circuit conductor between the DC source and the point of connection of the earthing electrode conductor.