Environmental specifications

Table 1: Standard specifications
Specification Value

Temperature range1

Operating

0°C to 55°C (32°F to 131°F)2

Nonoperating

-30°C to 60°C (-22°F to 140°F)

Relative humidity (noncondensing)

Operating

8% to 90% at 28°C (82.4°F) maximum wet bulb temperature

Non-Operating

5% to 95% at 38.7°C (101.7°F) maximum wet bulb temperature

1

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 304.8 m (1.8°F per 1,000 ft) to 3,048 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). No restrictions on product configurations. Not rated for operation over 3,048 m (10,000 ft).

2

Fan failure might reduce performance.

Table 2: ASHRAE Class A4 specifications

Specification

Value

Temperature range1

Operating

0°C to 45°C (32°F to 113°F)

10°C to 35°C (50°F to 95°F) when GPU is installed2

Nonoperating

-10°C to 60°C (-22°F to 140°F)

Relative humidity (noncondensing)

Operating

8% to 90% at 28°C (82.4°F) maximum wet bulb temperature

Non-Operating

5% to 95% at 38.7°C (101.7°F) maximum wet bulb temperature

1

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 125 m (1.8°F per 410 ft) to 900 m (2,953 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). No restrictions on product configurations except for rotating hard drives. PCI cards must be rated for continuous operation with 60°C cooling air. Not rated for operation over 3,048 m (10,000 ft).

2

Fan failure might reduce performance.

Table 3: Extended Edgeline specifications

Specification

Value

Temperature range1

Operating

0°C to 55°C (32°F to 131°F)

Nonoperating

-30°C to 60°C (-22°F to 140°F)

Relative humidity (noncondensing)

Operating

8% to 90% at 28°C (82.4°F) maximum wet bulb temperature

Non-Operating

5% to 95% at 38.7°C (101.7°F) maximum wet bulb temperature

1

All temperature ratings shown are for sea level. An altitude derating of 1.0°C per 305 m (1.8°F per 1,000 ft) to 3,048 m (10,000 ft) is applicable. No direct sunlight allowed. Maximum rate of change is 20°C per hour (36°F per hour). No restrictions on product configurations except for rotating hard drives. PCI cards must be rated for continuous operation with 60°C cooling air. Solid-state drives must be rated for continuous operation with 65°C cooling air. Not rated for operation over 3,030 m (10,000 ft).