Torque specifications for DC power connections

Be sure all DC power connections are connected at the proper torque setting shown in Table 4: Torque Specifications for DC Power Connections.

NOTE:

Refer to the appropriate hardware installation manual for torque specifications that are specific to your system.


Table 4: Torque Specifications for DC Power Connections

Connection

Tool

Torque

Breaker panel Terminals 1–3

11mm or 7/16” socket driver

50 in-lbs

Breaker panel Terminals 4–7

8 mm or 5/16” socket driver

20 in-lbs

Breaker panel Input and ground studs

14 mm or 9/16” socket driver

200 in-lbs

Breaker panel ground cable to rail

10 mm or 13/32” socket driver

40 in-lbs

Fuse panel GMT terminals

#2 Phillips driver

8 in-lbs

Fuse panel TPA terminals

8 mm or 5/16” socket driver

20 in-lbs

Fuse panel input terminals

11mm or 7/16” socket driver

50 in-lbs

Fuse panel ground cable

depends on screws provided

40 in-lbs

Fuse panel ground cable to rail

10 mm or 13/32” socket driver

40 in-lbs